Explore the model. Derive the result. Check its limits.
What you’ll be able to do
Classify before lookup.
Read the headings and units.
Interpolation is a local approximation.
Before you touch the controls
At 200 kPa, is water at 275°C a mixture or superheated vapor?
An experiment you can change
Interpolate a superheated-water table
Predict the direction of change, move one control, then explain the response using the equation.
h=2971.3+50275−250(3072.1−2971.3)=3021.7kJ/kg
Saturation at 200 kPa is 120.21 °C. This entire control range is superheated. At an exact row no interpolation is needed.
Model assumptions and units
Superheated water at 200 kPa. Interpolation is linear between the displayed IAPWS-IF97 table rows; values are not interpolated across phase boundaries.
h=ha+Tb−TaT−Ta(hb−ha)
Superheated water at 200 kPa · IAPWS-IF97
Temperature (°C)
h (kJ/kg)
u (kJ/kg)
v (m³/kg)
200
2,870.779
2,654.676
1.080519
250
2,971.259
2,731.477
1.198909
300
3,072.084
2,808.838
1.316231
350
3,173.891
2,887.299
1.432964
01
Classify before lookup.
Compare the specified temperature with saturation temperature at the specified pressure. A lower temperature indicates compressed liquid, an equal temperature allows saturation, and a higher temperature indicates superheated vapor. At saturation, another independent property is needed to determine phase proportions.
T<Tsat: liquid;T>Tsat: vapor
02
Read the headings and units.
Specific volume is volume per mass. Internal energy and enthalpy are also listed per mass. Subscripts f and g denote saturated liquid and vapor; fg denotes their difference. Multiply specific quantities by mass to obtain totals.
V=mv,U=mu,H=mh
03
Interpolation is a local approximation.
Between two rows at the same pressure and within the same phase, linear interpolation uses the fraction of the temperature interval traversed. It assumes the property curve is sufficiently close to a line over that interval.
h(T)=ha+Tb−TaT−Ta(hb−ha)
04
Avoid interpolation through a phase boundary.
A compressed-liquid row and a superheated row cannot be blended as if boiling were an ordinary temperature interval. First identify the region, then use the corresponding property relation. For mixtures, use quality and saturated endpoints.
A worked example
Interpolate at 275°C and 200 kPa.
Saturation at 200 kPa is about 120.21∘C; 275°C is superheated.
The temperature is halfway between 250°C and 300°C: (275−250)/(300−250)=0.5.
Use h275=h250+0.5(h300−h250) with the table displayed below. The live marker shows the interpolated result.
Make the idea your own
Calculate. Compare. Test the assumptions.
Work out your answer, check it, then explore the visual solution. The answer checker uses a 1.5% rounding tolerance; for model-limit questions it checks the displayed model result.
1 · Calculate
A midpoint table lookup
At 200 kPa and 275°C, find specific enthalpy by interpolation in the displayed table.
Hint
The requested temperature lies halfway between 250 and 300°C.
Explore the visual solution
h=2971.3+50275−250(3072.1−2971.3)=3021.7kJ/kg
Saturation at 200 kPa is 120.21 °C. This entire control range is superheated. At an exact row no interpolation is needed.
Model assumptions and units
Superheated water at 200 kPa. Interpolation is linear between the displayed IAPWS-IF97 table rows; values are not interpolated across phase boundaries.
h=ha+Tb−TaT−Ta(hb−ha)
Controls explore variations. The steps below retain the original question’s values.
Superheated water at 200 kPa. Interpolation is linear between the displayed IAPWS-IF97 table rows; values are not interpolated across phase boundaries.
h=ha+Tb−TaT−Ta(hb−ha)
2 · Compare
A quarter of an interval
At 200 kPa and 212°C, find interpolated specific enthalpy. Does averaging the endpoint values equally give the correct result?
Hint
Use (212 − 200)/(250 − 200), not 1/2.
Explore the visual solution
h=2870.8+50212−200(2971.3−2870.8)=2894.9kJ/kg
Saturation at 200 kPa is 120.21 °C. This entire control range is superheated. At an exact row no interpolation is needed.
Model assumptions and units
Superheated water at 200 kPa. Interpolation is linear between the displayed IAPWS-IF97 table rows; values are not interpolated across phase boundaries.
h=ha+Tb−TaT−Ta(hb−ha)
Controls explore variations. The steps below retain the original question’s values.
Superheated water at 200 kPa. Interpolation is linear between the displayed IAPWS-IF97 table rows; values are not interpolated across phase boundaries.
h=ha+Tb−TaT−Ta(hb−ha)
3 · Challenge the model
An exact table row
Find enthalpy at 200 kPa and 350°C. Explain why no temperature interpolation is needed and why pressure must still match.
Hint
An exact row can be used directly, but only in the correct pressure table.
Explore the visual solution
h=3173.9+1350−350(3173.9−3173.9)=3173.9kJ/kg
Saturation at 200 kPa is 120.21 °C. This entire control range is superheated. At an exact row no interpolation is needed.
Model assumptions and units
Superheated water at 200 kPa. Interpolation is linear between the displayed IAPWS-IF97 table rows; values are not interpolated across phase boundaries.
h=ha+Tb−TaT−Ta(hb−ha)
Controls explore variations. The steps below retain the original question’s values.
Superheated water at 200 kPa. Interpolation is linear between the displayed IAPWS-IF97 table rows; values are not interpolated across phase boundaries.
h=ha+Tb−TaT−Ta(hb−ha)
Your learning path
Ready to carry this forward?
Mark this lesson complete when you can explain the main idea and work through its practice. Completion is your choice.